SECURITHERM sequential thermostatic basin mixer
The Delabie SECURITHERM H9600 is a deck-mounted thermostatic basin mixer developed for hospitals, clinics and care homes. The lever opens on cold water and moves towards warm, with temperature capped at 40 °C, so a careless movement cannot deliver hot water. Smooth internal surfaces with a low water volume reduce the places where bacteria can grow.
Product details
- Sequential operation: one lever for flow and temperature; opens and closes on cold water
- Temperature: from cold up to 40 °C, limiter set at 40 °C
- Safety: shuts off instantly if the cold or hot supply fails; Securitouch thermal insulation prevents burns from the body
- Flow rate: limited to 5 l/min at 3 bar
- Hygiene: smooth-bore body and spout with low water volume, no non-return valves on the inlets and no cross-flow between hot and cold; thermal and chemical shock possible
- Ergonomics: 146 mm hygienic lever that can be operated with an elbow or forearm
- Warranty: 30 years
Benefits
- Patient safety: no scalding, even if the cold supply fails
- Hygiene: fewer places for biofilm, thermal shock without dismantling
- Hands-free use: long lever for staff and people with reduced mobility
Thermostatic or pressure-balancing
The SECURITHERM H9600 controls temperature with a thermostatic cartridge, while SECURITHERM EP mixers balance hot and cold pressure. The thermostatic version suits sites where hot water temperature fluctuates or a strictly defined limit is needed, such as paediatric and geriatric wards.
Where it is used
- hospitals and clinics: patient rooms, consulting rooms, nurse stations
- care and nursing homes
- rehabilitation centres
- nurseries and crèches
- accessible washrooms in public buildings
Technical specifications
| Feature | Value |
|---|---|
| Manufacturer | Delabie |
| Technology | SECURITHERM sequential thermostatic |
| Temperature range | cold – 40 °C |
| Temperature limiter | 40 °C |
| Flow rate | 5 l/min at 3 bar |
| Height | 95 mm |
| Spout length | 120 mm |
| Lever length | 146 mm |
| Material | chrome-plated brass |
| Connection | F3/8", F3/8" PEX flexibles and chrome-plated brass stopcocks (H9600) |
| Fixing | reinforced by two stainless steel rods |
| Certificates | ACS, WRAS, PZH, DoP, TMV3 |
| Warranty | 30 years |
Variants
- ref. H9600 – no pop-up waste, 146 mm lever, flexibles and stopcocks
- ref. H9601 – with pop-up waste, 146 mm lever, flexibles and stopcocks
- ref. H96001 – no pop-up waste, 146 mm lever, flexibles, no stopcocks
FAQ
Why is there no pop-up waste?
The H9600 comes without a pop-up, a common choice in healthcare where basins are not filled and fewer dirt traps matter. Delabie pairs it with the HYGIÉNA hygienic waste ref. 611. If a pop-up is needed, choose H9601.
Can it be thermally disinfected?
Yes, Delabie states that thermal and chemical shocks are possible. Follow the site's Legionella control protocol.
Which cartridge is replaced during servicing?
Delabie lists the basin thermostatic cartridge ref. N960 as the spare part. Spare parts are available on request.
Related products
- ref. 611 – HYGIÉNA hygienic basin waste
- ref. N960 – basin thermostatic cartridge (spare part)
- ref. H9630 – SECURITHERM sequential thermostatic shower mixer
- ref. H9739 – SECURITHERM dual control thermostatic shower mixer
- ref. 2610EP – wall-mounted pressure-balancing basin mixer
Request a quote for your project or volume order.